UDC Series
1kVA-3kVA
UDC 1-3kVA is an online double-conversion UPS providing consistent sine-wave power to your critical equipment. It supports personal computers, networks, servers, VoIP and telecommunications. With full digital control, ECO mode and compact design, it features high reliablity and energy savings. Optional external battery pack can be connected for longer backup time to keep your applications safe and running smoothly at all times.
General Features
■ Online double conversion,
■ Wide input voltage range (110~300Vac)
■ Input power factor 0.99
■ Output power factor 0.9
■ Maximum 12A charger for long-run models
■ Charging current can be set by LCD(Long run unit)
■ 50Hz/60Hz frequency converter mode
■ Emergency power off function (EPO)
■ ECO mode operation for energy saving
■ Generator compatible
■ SNMP + USB + RS232 multiple communications
■ Smart battery charger design for optimized battery performance
■ Selectable output voltage: 200,208,220,230,240Vac
Technical Specification
MODEL | UDC9101S / UDC9101H | UDC9102S / UDC9102H | UDC9103S / UDC9103H | |||||||||||
Capacity (VA/Watts) | 1000VA / 900W | 2000VA / 1800W | 3000VA / 2700W | |||||||||||
Phase | Single phase with grounde with ground | |||||||||||||
INPUT | ||||||||||||||
Nominal Voltage | 200/208/220/230/240Vac | |||||||||||||
Operating voltage range | Lower limit of input voltage | 160Vac±5% @100%~80%load 140Vac±5% @80%~70%load 120Vac±5%@70%~60%load 110Vac±5%@60%~0%load (Ambient temp. <35℃) | ||||||||||||
Lower limit of input voltage | 175Vac±5% @100%~80%load 155Vac±5% @80%~70%load 135Vac±5% @70%~60%load 125Vac±5% @60%~0%load(Ambient temp. <35℃) | |||||||||||||
Upper limit of input voltage | 300Vac±5% | |||||||||||||
Upper comeback voltage from bypass mode to normal mode | 290Vac±5% | |||||||||||||
Input Voltage Range | 55~150Vac or 110~300Vac @ 60% load, 80~145Vac or 160~300Vac @ 100% load | |||||||||||||
Operating frequency range | 40~70Hz | |||||||||||||
Power Factor | 0.99 | |||||||||||||
Generator input | Support | |||||||||||||
OUTPUT | ||||||||||||||
Output Voltage | 200/208/220/230/240Vac | |||||||||||||
Power Factor | 0.9 | |||||||||||||
Voltage Regulation | ±1% | |||||||||||||
Frequency | Line mode (Synchronized range) | 47~53Hz or 57~63Hz | ||||||||||||
Bat. mode | (50/60±0.1)Hz | |||||||||||||
Crest Factor | 3:1 | |||||||||||||
Harmonic Distortion (THDv) | ≤3% THD (Linear load) | |||||||||||||
≤6% THD (Non-linear load) | ||||||||||||||
Waveform | Pure Sinewave | |||||||||||||
Transfer Time | AC mode <->Batt. Mode | Zero | ||||||||||||
Inverter <-> Bypass | 4ms(Typical) | |||||||||||||
EFFICIENCY | ||||||||||||||
AC Mode | 88% | 92% | 92% | |||||||||||
Battery Mode | 85% | 86% | 87% | 88% | 89% | 90% | ||||||||
BATTERY | ||||||||||||||
Battery Type | 12V9AH | Depends on the capacity of external batteries | 12V9AH | Depends on the capacity of external batteries | 12V9AH | Depends on the capacity of external batteries | ||||||||
Numbers | 2 | 2 | 3 | 4 | 4 | 6 | 6 | 6 | 8 | |||||
Backup time | Long run unit depends on the capacity of external batteries | |||||||||||||
Typical recharging time(Standard modle) | 4 hours recover to 90% capacity | |||||||||||||
Charging voltage | 27.4/41.1Vdc±1% | 27.4/41.1Vdc±1% | 41.0Vdc±1% | 54.7Vdc±1% | 54.7Vdc±1% | 82.1Vdc±1% | 82.1Vdc±1% | 82.1Vdc±1% | 109.4Vdc±1% | |||||
Charging current(max.) | 1.0A | 12A max,can be set by LCD | 1.0A | 12A max,can be set by LCD | 1.0A | 12A max,can be set by LCD | ||||||||
SYSTEM FEATURES | ||||||||||||||
Line mode Battery mode | Ambient temp.<35℃ | 105%~110%: UPS shuts down after 10 minutes at battery mode or transfer to bypass when the utility is normal 110%~130%: UPS shuts down after 1minute at battery mode or transfer to bypass when the utility is normal >130%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal | ||||||||||||
35℃ |
105%~110%: UPS shuts down after 1 minutes at battery mode or transfer to bypass when the utility is normal >110%:UPS shuts down after 3 seconds at battery mode or transfer to bypass when the utility is normal | |||||||||||||
Short circuit | Hold whole system | |||||||||||||
Overheat | Line mode: Switch to bypass; Backup mode: Shut down UPS immediately | |||||||||||||
Battery low | Alarm and switch off | |||||||||||||
EPO (optional) | Shut down UPS immediately | |||||||||||||
Audible & Visual alarms | Line failure, Battery low, Over load, System fault | |||||||||||||
Communication interface | USB (or RS232), SNMP card (optional), Relay card (optional) | |||||||||||||
PHYSICAL | ||||||||||||||
Dimension W×H×D (mm) | 144×209×293 | 144×209×293 | 144×209×293 | 144×209×399 | 144×209×399 | 144×209×399 | 191×337×460 | 144×209×399 | 144×209×399 | |||||
Net Weight (kg) | 9.8 | 4 | 4.1 | 17 | 6.7 | 6.8 | 27.6 | 7.3 | 7.4 | |||||
ENVIRONMENT | ||||||||||||||
Operating temperature | 0~40℃ | |||||||||||||
Storage temperature | -25℃~55℃ | |||||||||||||
Humidity range | 20~90% RH @ 0~40℃ (Non-condensing) | |||||||||||||
Altitude | <1500m | |||||||||||||
Noise Level | Less than 50dBA @ 1 Meter | |||||||||||||
STANDARDS | ||||||||||||||
Safety | IEC/EN62040-1,IEC/EN60950-1 | |||||||||||||
EMC | IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,IEC61000-4-5,IEC61000-4-6,IEC61000-4-8 |