Home >  Products > Data Center Infrastructure > UPS> Online Transformerless Commercial UPS> UCR (6-10kVA)
UCR
6-10kVA
  
UCR60-100 series UPS is a Rack/Tower convertible UPS solutions which integrates true double-conversion design, DSP technology to provide clean high-level quality power as well as better voltage conditions to different application. What's more, with N+X parallel redundancy, it can achieve higher availability and MTBF (mean time between failure) to fully protect mission-critical devices.
  • UCR (6-10kVA)

General Features

● True double-conversion

● Rack-mounted and floor-standing tower can be convertible

● LCD panel can be rotated according to the type of deployment

● DSP technology guarantees high reliability

● N+X parallel redundancy

● Compatible with 3 phases and single phase input

● Selectable quantity of battery for each group:16/18/20 pieces

● Adjustable charging current via LCD

● 3-stage charging design optimizes battery performance

● ECO mode operation for energy saving

● Self-diagnosis at startup

● Emergency power off function(EPO)

● Maintenance bypass is convenient for maintenance

● Generator compatible

● Communications:RS-232,USB,Parallel card(Optional),SNMP card(Optional), Relay card (Optional)

● Cold start

Technical Specification
MODEL UCR60L UCR100L
Capacity (VA/Watts) 6K / 5.4K 10K / 9K
INPUT 
Nominal Voltage 380/400/415Vac(3Ph+N+PE) or 220/230/240Vac(L+N+PE) 
Operating Voltage
 Range
208~478Vac or 120VAC-276Vac
Operating Frequency
 Range
50Hz:45~55Hz,60Hz:54~66Hz
Power Factor ≥0.99
Bypass Voltage
 Range
Max.voltage: 220V:+25%(Optional +10%,+15%,+20% )
         230V:+20%(Optional +10%,+15%)
240V:+15%(Optional +10% )
   Min. voltage: -45% (Optional -20%,-30%)
ECO Range Same as bypass
Harmonic
Distortion (THDi)
≤5%(100% non-linear load) 
OUTPUT  
Output Voltage 220/230/240Vac
Power Factor 0.9
Voltage Regulation ±1%
Frequency Line Mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(Optional)
Bat.Mode (50/60±0.1)Hz
Crest Factor 3:1
Harmonic
 Distortion (THD)
≤2% with linear load
≤5% with non-linear load 
Waveform  Pure Sinewave
Transfer Time Utility to Battery : 0ms; Utility to Bypass: 0ms
EFFICIENCY
Efficiency Up to 94%
BATTERY
Battery Voltage Selectable Voltage: ±96/108/120Vdc
Typical Recharge Time 6-8 hours (To 90% capacity)
Charging Current  Maximum current 10A
PROTECTION
Overload Line Mode Load≤125%: last 5min;≤150%: last 1min;>150% 200ms turn to bypass mode
Bypass Mode 40A(Input breaker) 63A(Input breaker)
Short Circuit Hold Whole System
Overheat Line Mode: Switch to Bypass; Backup Mode: Shut down UPS immediately
Battery Low Alarm and Switch off
INDICATORS
Audible &Visual Alarms Line Failure, Battery Low, Overload, System Fault
Status LED &LCD Display Line Mode, Backup Mode, Eco Mode, Bypass Mode, Battery Low, Battery Bad, Overload & UPS Fault
Parameters On
The LCD Panel
Input/Output Voltage, Input/Output Frequency, Load Level, Battery Level, Inner Temperature & Remaining Battery Backup Time
MANAGEMENT
Communication Interface RS-232,USB,Parallel card, SNMP card(Optional), Relay card (Optional)
ENVIRONMENT
Operating Temperature 0℃~40℃
Storage Temperature -25℃~55℃
Humidity Range 0~95% (Non-condensing)
Altitude < 1500m
Noise Level <55dB
PHYSICAL
Dimension W×H×D (mm) 443×131×580(3U)
Net Weight (kg) 30 31
STANDARDS
Noise Suppression Complies with EN62040-2
Safety  IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4,
IEC61000-4-5,IEC61000-4-6,IEC61000-4-8
BATTERY PACK
Model EXBR±120V
Battery type&
Max.quantity
7Ah×20/9Ah×20
Dimensions
 W×H×D (mm)
443×131×720(3U)
Net Weight (kg) 67