Modular UPS-Kstar HPM  Family
25-1560kVA
 
In order to save the wasted power of underutilized, over-size ordinary UPS, and obtain "N + 1" redundancy to ensure the critical system has high power availability,  data centers now choose modular UPS as their first choice for critical power protection. With Compact size,high efficiency and easy expansion according to power requirements. Modular UPS systems are growing fast in the three-phase market.

HPM series UPS(Uninterrutible power supply system)efficiency can be as high as 96.5%,minimizing UPS energy consumption.The module capacity is 6KVA-50kVA optional. The UPS system consists of 1 to 20 UPS modules connected in parallel and the number of UPS cab be flexibly increased with load. The modular design and the N + X parallel redundancy technology, making the expansion&management easier as well as reducing initial acquisition costs.
 
General Features

● Adopting digital control design, and the control system is more reliable

● High power density design, capacity of single power module is 6KVA/ 10KVA/ 15KVA/ 20KVA/ 25KVA/ 30KVA/ 40KVA, the height of all these modules is 3U.The power of system ranged from 6KVA to 520KVA corresponds to the number of parallel power modules from 1 to 13

 Redundant control system, each power module is equipped independent control system, and control itself independently according to the sharing message, and the fault module separates from the system automatically

 Support parallel expansion for cabinet, and  parallel expansion is up to 4 cabinets.

 Voltage of batteries can be configured flexibly, 1 input 1 output/ 3 input 1 output ±96Vdc/ ±108Vdc/ ±120Vdc(16/18/20PCS)selectable; 3 input 3 output±216Vdc/±228Vdc/±240Vdc (32/34/ 36/38/40PCS) selectable

 Intelligent charging mode, Charging current can be configured , there are 3 charging mode  which are constant current mode、constant voltage mode、floating charging mode, and the charging mode can be transfer smoothly.

Technical Specification
MODEL HPM3325-250KVA HPM3330-90KVA HPM3330-150KVA HPM3330-300KVA HPM3340-200KVA HPM3340-320KVA HPM3340-400KVA HPM3340-520KVA HPM3340-800KVA HPM3340-1280KVA  HPM3340-1560KVA
Capacity (VA/Watts) UPS cabinet  250k / 225k 90k / 81k  150k / 135k 300k / 270k 200k/180k 320k/288k 400k / 360k 520k / 468k 800k / 720k 1280k / 1152k 1560k / 1404k
HPM module    25k / 22.5k  25k / 22.5k, 30k / 27k 40k / 36k
INPUT
Nominal voltage 380/400/415Vac, (3Ph+N+PE) 
Operating voltage range 208~478Vac for half load; 305~478Va c for full load 
Operating frequency range 40~70Hz
Power factor ≥0.99
Harmonic distortion (THDi) 3%(100% non-linear load)
Bypass voltage range 380Vac Max.voltage: +25%(optional +10%,+15%,+20% )
400Vac Max.voltage: +20% (optional +10%,+15%)
415Vac Max.voltage: +15% (optional +10%)
Min.voltage: -45% (optional -20%,-30%)
Bypass frequency range  Frequency synchronize tracing range:±10%
Generator access Support
OUTPUT
Rated voltage 380/400/415Vac(3Ph+N+PE)
Power factor 0.9
Voltage regulation ±1%
Frequency Line mode ±1%/±2%/±4%/±5%/±10% of the rated frequency(optional)
Bat. mode (50/60±0.1%)Hz
Crest factor 3:1
Harmonic distortion (THDv) ≤2% with linear load
≤5% with non-linear load  
Efficiency 95.00%
BATTERY
Battery voltage ±192/±204/±216/±228/±240Vdc; Battery quantity(optional)
Charging current(A) UPS cabinet  60A (Max.) 30A (Max.) 50A (Max.) 100A (Max.) 50A (Max.) 80A (Max.) 100A (Max.) 130A (Max.) 200A (Max.) 320A (Max.) 390A (Max.)
HPM module  6A (Max.)   25kVA:6A (Max.) / 30kVA:10A (Max.) 10A (Max.)
Backup time  Depends on the capacity of external batteries
SYSTEM FEATURES
Transfer time Utility to battery:0ms; Utility to bypass:0ms
Overload Line mode Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% turn to bypass mode immediately
Bat. mode Load≤110%: last 10min,≤125%: last 1min,≤150%: last 1S,≥150% shut down UPS immediately Load≤110%: last 60min,≤125%: last 10min,≤150%: last 1min,≥150% shut down UPS immediately
Bypass mode  Breaker (25kVA:40A)  Breaker ( 25kVA:40A / 30kVA:60A)  40kVA:95A
Short circuit Hold whole system
Noise suppression Complies with EN62040-2
Communication interface UPS cabinet : RS232, RS485, Dry contact, Intelligent slot x 2(SNMP card,Relay card optional);
HPM series UPS module: RS232 
ENVIRONMENT
Operating temperature 0~40℃
Storage temperature -25~55℃
Humidity range 0~95% (Non-condensing)
Altitude <1500m. When >1500m, derating power for use
Noise level <70dB <65dB <70dB <73dB
PHYSICAL
Dimension D×W×H (mm) UPS cabinet  1100×600×2000  840×600×1400 1100×600×2000  850×600×1600 850×600×2000  850×1200×2000 850×2000×2000 850×3400×2000 4800×850×2000 
HPM module  443x580x131 (3U)
Net weight (kg) UPS cabinet  290 158 170 307 251 320 540 980 1400 2800
HPM module 32    25kVA/32; 30kVA/33.5 36
STANDARDS
Safety  IEC/EN62040-1,IEC/EN60950-1
EMC IEC/EN62040-2,IEC61000-4-2,IEC61000-4-3,IEC61000-4-4, IEC61000-4-5,IEC61000-4-6,IEC61000-4-8