Home >  Products > Data Center Infrastructure > Precision Cooling> In-Row Precision Cooling> Kstar In-Row Cooling Unit-FocusAir Family
Kstar In-Row Cooling Unit-FocusAir Family
Designed for the special cooling requirement of new generation high heat density data center. Close matching to the data center racks, this new generation in-row cooling system features new air distributing path, real-time rack temperature monitoring, dynamic cooling output and modular size, to serve data center with high reliability, high efficiency, flexibility and predictability. 
Application: High power-density data center
General Features

● Total cooling capacity: 25kW~70kW

● FocusAir In-Row cooling system is compatible with multiple temperature sensors, monitoring the heat load change and directly control the supply air temperature, that is safe, reliable, and energy saving, making sure that the inlet air temperature of servers conform to the requirements and the equipment running in the best condition

● Dimension matches the cabinet, and it supports top and bottom pipes

● Inverter compressor, EC fan and electronic expansion valve are standard equipment for FocusAir series

● Dynamic coordination output :The FocusAir refrigeration system works based on the change of the heat load, dynamic coordinates cooling capacity output and air volum output of the unit, realizes real-time matching with the load change to keep the unit running in the best condition

● Redundant fan design: replacing the fault fan without affecting the running of FocusAir

● First class components make FocusAir more stable

● Dimension of FocusAir series is the same with cabinets' , so it look very beautiful

● Fluorine pump can save more than 50% energy by using nature cold source

Technical Specification
DX Unit  
FS*** unit 20 25 40
 Unit Configuration  -  Single Cooling Constant 
Temperature
 and Humidity
 Single Cooling  Contant
 Temperature
 and Humidity
 Single Cooling Constant 
Temperature
 andHumidity
Total Cooling 
Capavity
kW 25.1 25.5 40.4
Sensible Cooling
 Capavity
kW 25.1 25.5 40.4
Air volume m³/h 4920 5050 8080
Sensible heat ratio / 1 1 1
Heating capacity KW   3   3   6
Humidyfying capacity  kg/h   3   3   3
Number of
 compressors
Pcs 1 1 1
Number of Fans Pcs 6 3 3
Voltage V 380~415 380~415 380~415
Frequency Hz 50 50 50
Phase P 3 3 3
Full-load 
 Current 
A 22.7 27.3 24.8 29.4 29.4 38.5
Unit Weight kg 230 237 255 262 305 315
Unit Width mm 300 400 600
Unit Depth mm 1100
Unit Height mm 2000
DX Unit  
FS*** unit 25 35 65
 Unit Configuration  -  Single Cooling Constant
 Temperature
 and Humidity
 Single Cooling  Contant
 Temperature
 and Humidity
 Single Cooling Constant
 Temperature
 and Humidity
Total Cooling
 Capavity
kW 25.1 35.5 67
Sensible Cooling
 Capavity
kW 25.1 35.5 67
Air volume m³/h 5100 6500 12000
Sensible heat
 ratio
/ 1 1 1
Water inlet
 Capavity
m³/h 4.7 6.5 12
Pressure drop kpa 45 55 60
Heating capacity KW   3   3   6
Humidyfying capacity  kg/h   3   3   3
Number of Fans Pcs 6 3 3
Voltage V 200~240 380~415 200~240 380~415 380~415
Frequency Hz 50 50 50
Phase P 1 3 1 3 3
Full-load Current  A 9.3 22.9 5.3 18.9 5.3 14.4
Size of inlet and
 outlet water pipes
mm 28 32 42
Unit Weight kg 190 196 215 223 267 275
Unit Width mm 300 400 600
Unit Depth mm 1100
Unit Height mm 2000
    Note
               parameter table
               Air/water cooled unit data based on 37°C,25%RH indoor return air temperature。
               Chilled water unit data based on 37°C,25%RH indoor return air temperature。The intel and outlet water temperature of chilled water
 are 10°C and 15°C
               The noise data is sound pressure level value of 10m free field
               Standard outdoor unit minimum working temperature -20°C Low temperature unit minimum working temperature -40°C Standrd Unit with front air supply
               Specifications are subject to change without prior notice